Skip to content

Sag and tension calculator: conductor in a span over temperature

Choose the conductor, enter span and initial state: the tool gives sag, tension and conductor length from −20 to +80 °C, the stringing sag at the conductor temperature on the day and the state with ice load.

Register for free Read more in the manual

1 location free, no payment details. Runs in the browser – nothing to install. Try it without registering

Span in the tool: stringing sag, greatest sag, greatest tension, conductor curves and checklist
Example from the sample project

What the tool calculates

Sag table

Sag, horizontal tension, greatest conductor tension and length per temperature – to print and copy.

Stringing sag

A separate row for the conductor temperature on the day of installation.

Span to the next tower

Span from the coordinates of the locations; the tool suggests the height difference from terrain, foundation and tower assembly.

Conductors from the table

Common aluminium-steel conductors with diameter, weight, breaking load, modulus of elasticity and expansion – or your own values.

How to proceed

  1. Create the span. On the project page choose “Calculate span” between two locations – the span comes from the coordinates.
  2. Enter conductor and initial state. Choose the conductor; fix the initial state by share of breaking load, tension or sag.
  3. Read the table. The conductor temperature on the day has its own row in the table.
  4. Look at it in the profile. The greatest sag of the table is shown in the project's line profile above the terrain.

Inputs, results and calculation method

What you enter

  • Conductor from the table or own conductor data
  • Span, height difference, ruling span
  • Initial state: share of breaking load, tension or sag at a temperature
  • Conductor temperature when sagging, ice load, permissible tension
  • For the profile: length of the suspension string, crossing objects in the span

What you get

  • Sag, tension and conductor length from −20 to +80 °C
  • Stringing sag and tension on the day
  • Greatest tension and greatest sag, with ice load
  • Conductor curves in the span, checklist, table to print
  • Hand-over to the project's line profile

How it is calculated

  • Catenary with c = H ÷ w: sag f = c · (cosh(a ÷ 2c) − 1) ≈ w · a² ÷ (8 · H); length L = 2c · sinh(a ÷ 2c).
  • Change of state between two temperatures and loads: change-of-state equation with the conductor's modulus of elasticity and thermal expansion, calculated with the ruling span.
  • With attachment points at different heights the sag is the vertical distance to the chord at mid-span.

Catenary and change-of-state equation are textbook formulas of overhead line calculation. The conductor data come from a manufacturer's table. The complete formulas are in the manual. Go to the chapter in the manual

An example, recalculated

Conductor 243-AL1/39-ST1A, span 300 m, 20 % of the breaking load at +10 °C. The figures are calculated by the same engine as in the application – when this page is opened.

Conductor
243-AL1/39-ST1A (21.8 mm, 0.985 kg/m)
Span
300 m
Initial state
horizontal tension 20 % of the breaking load at +10 °C
Conductor temperature when sagging
+15 °C
QuantityResultCalculation
Sag in the initial state6.29 mcatenary with H = 17.28 kN
Stringing sag at +15 °C6.48 mchange-of-state equation; horizontal tension 16.78 kN
Greatest sag8.77 mat +80 °C
Greatest conductor tension21.19 kNat -20 °C, at the attachment point
Conductor length in the span300.35 min the initial state

The sag table in the tool lists the temperatures from −20 to +80 °C, the initial state, the conductor temperature when sagging and – if entered – the ice load.

Estimate the sag

No login, nothing saved: enter values, and the result is calculated by the same engine as in the application.

Sag at +15 °C
6.48 m in the initial state 6.29 m
Horizontal tension
16.78 kN 19 % of the breaking load
Tension at the attachment point
16.84 kN
Conductor length in the span
300.37 m
Greatest sag of the table
8.77 m at +80 °C

One span with attachment points at equal height, without ice load. In a project: sag table from −20 to +80 °C, height difference, ruling span, ice load and the line profile above the terrain.

Save in a project – with PDF, 3D and team

Limits

What the tool does not do – so that it is clear what the result is good for. Results are planning aids, not construction documents.

  • Not included: creep and settling of new conductors, wind, the swing of insulator strings, unequal stresses in the spans of a section, conductor vibration.
  • The permissible tension is an input. The ice load is an input or follows from the chosen ice load zone (E1 to E4) and the conductor diameter; the grading of the zones is an assumption and must be compared with the line design. The wind zone is information only – wind is not part of the calculation.
  • The tool replaces neither a line design calculation nor the designer's stringing table.
  • The change-of-state equation uses the parabola – accurate enough up to a sag of about one tenth of the span; above that the checklist points it out.

Frequently asked questions

How large is the sag at a span of 300 m?

That depends on conductor and tension. A 243-AL1/39-ST1A strung at +10 °C with 20 % of the breaking load sags 6.29 m – at +80 °C it is 8.77 m.

What is the stringing sag?

The sag to which the conductor is set on the day of installation – depending on the conductor temperature that day. The tool shows it as a separate row.

Does the tool check clearances to the ground?

Not the span on its own. The project's line profile shows the conductor line above the terrain and gives the smallest clearance – as a planning aid, not as a verification.

Try it on your next construction project.

One location free, all tools. No credit card, no subscription.

Register for free