Sag, horizontal tension, greatest conductor tension and length per temperature – to print and copy.
Choose the conductor, enter span and initial state: the tool gives sag, tension and conductor length from −20 to +80 °C, the stringing sag at the conductor temperature on the day and the state with ice load.
Register for free Read more in the manual
1 location free, no payment details. Runs in the browser – nothing to install. Try it without registering
Sag, horizontal tension, greatest conductor tension and length per temperature – to print and copy.
A separate row for the conductor temperature on the day of installation.
Span from the coordinates of the locations; the tool suggests the height difference from terrain, foundation and tower assembly.
Common aluminium-steel conductors with diameter, weight, breaking load, modulus of elasticity and expansion – or your own values.
Catenary and change-of-state equation are textbook formulas of overhead line calculation. The conductor data come from a manufacturer's table. The complete formulas are in the manual. Go to the chapter in the manual
Conductor 243-AL1/39-ST1A, span 300 m, 20 % of the breaking load at +10 °C. The figures are calculated by the same engine as in the application – when this page is opened.
| Quantity | Result | Calculation |
|---|---|---|
| Sag in the initial state | 6.29 m | catenary with H = 17.28 kN |
| Stringing sag at +15 °C | 6.48 m | change-of-state equation; horizontal tension 16.78 kN |
| Greatest sag | 8.77 m | at +80 °C |
| Greatest conductor tension | 21.19 kN | at -20 °C, at the attachment point |
| Conductor length in the span | 300.35 m | in the initial state |
The sag table in the tool lists the temperatures from −20 to +80 °C, the initial state, the conductor temperature when sagging and – if entered – the ice load.
No login, nothing saved: enter values, and the result is calculated by the same engine as in the application.
One span with attachment points at equal height, without ice load. In a project: sag table from −20 to +80 °C, height difference, ruling span, ice load and the line profile above the terrain.
What the tool does not do – so that it is clear what the result is good for. Results are planning aids, not construction documents.
That depends on conductor and tension. A 243-AL1/39-ST1A strung at +10 °C with 20 % of the breaking load sags 6.29 m – at +80 °C it is 8.77 m.
The sag to which the conductor is set on the day of installation – depending on the conductor temperature that day. The tool shows it as a separate row.
Not the span on its own. The project's line profile shows the conductor line above the terrain and gives the smallest clearance – as a planning aid, not as a verification.
All tools work at the same location with the same coordinate – what is created in one is available in the next.