10 Span (conductor)
A conductor in a span: sag, tension and conductor length in the initial state, at every conductor temperature and with ice load – as a sag table with the stringing sag for the day of installation.
Creating, calculating, saving
- Create: on the project page, Calculate span in the row of a location – or on the location page, the card Span (conductor) › Create span and calculate. The span sits at the location where it starts and leads to the next location of the project; there is one per location. The card then shows destination, conductor, span length, maximum sag, maximum conductor tension and stringing sag, and Open takes you back.
- From … to: the selection at the top of the section Span lists the other locations of the project with their straight-line distance. If you choose one, the span length comes from the coordinates of both locations; it stays editable – if it differs, the page says so. free leaves the span length entirely as an input. You always enter the height difference of the attachment points yourself.
- Calculate: at the left the inputs in four groups – Conductor, Span, Initial state, Further states –, at the right the result. Every change is calculated immediately. For an input that is not permitted, the page names the field and the range; the last valid result stays visible, faded.
- Save or CtrlS stores inputs and result at the location; the time is shown next to it. If someone else has saved in the meantime, the page reports this and overwrites nothing.
- Delete: on the location page in the menu ⋯ of the card. With the location, its span is deleted, moved or archived as well.
- Whoever has read-only access in the project can view and calculate but not save.
Inputs
- Conductor
- one of 28 aluminium conductors, steel-reinforced (table below) – or enter own conductor data: diameter, weight in kg/km, total cross-section, breaking load, modulus of elasticity and coefficient of linear expansion from the data sheet. This also covers aluminium, alloy, copper and earth wires.
- Span length
- horizontal distance between the two attachment points in m.
- Height difference
- of the attachment points in m; positive if the right one is higher. Empty means level.
- Ruling span
- only if the span is part of a tension section with several spans: √(Σa³ ÷ Σa) over all spans of the section. If empty, the calculator uses the span length.
- Initial state
- the conductor temperature and one value that fixes the tensile stress at this temperature – either the horizontal tension as a share of the breaking load in %, the horizontal tension in kN or the sag in this span (measured, for example, or from the sag table).
- Conductor temperature when sagging
- the temperature of the conductor on the day of stringing. The sag table gets its own highlighted row for it.
- Ice load zone
- E1 to E4 or none. With a zone the calculator works out the ice load itself: multiple × (5 + 0.1 · d) in N/m, with the conductor diameter d in mm and 1, 2, 3 or 4 times for E1 to E4 (German ice load zones). Which zone applies is laid down by the line design or the grid operator. The checklist states the ice load used.
- Ice load at −5 °C
- only without an ice load zone: additional load in N/m, from the line design. If empty, no state with ice is calculated.
- Wind zone
- 1 to 4 or not stated (German wind zones). The zone appears with wind speed and velocity pressure in the checklist and on the sheet – as information for the line design. Wind is not part of the calculation. The official notice of the federal state is binding; the table “Zuordnung der Windzonen nach Verwaltungsgrenzen” of the German building authority DIBt summarises it.
- Suggestion from the position
- If the location has a coordinate in Germany, a suggestion appears above the two fields – for the span from this location and the location at the other end, the less favourable value of each. A new span starts with the suggestion; Apply suggestion sets it again later. Near a boundary means: within about 1 km there is another zone or class.
- Wind zone: per municipality from the DIBt table (as of 2 June 2022). Where the table does not separate by municipality (“right of the Moselle”, “municipalities on Lake Constance up to 3 km inland”) or names municipalities that no longer exist as such, two zones are shown; the higher one is suggested.
- Ice load and ice load zone: the class of the map “ice loads for overhead lines (conductors up to 30 mm diameter, up to 30 m above ground)” of the German Weather Service – 0–5, 5–10, 10–15, 15–20, 20–40, 40–100, over 100 N/m. From it the zone by the limits 13 / 23 / 33 N/m with which a VDE|FNN note (12/2017) assigns observed ice loads to the zones. The classes 10–15 and 20–40 N/m cover several zones; the range is then shown.
- For the longitudinal profile
- Length of the insulator string (suspension string below the cross-arm; empty = conductor at the cross-arm) and up to four crossed objects in the span – name, distance from the start of the span, height above ground. Neither enters the conductor calculation: the longitudinal profile on the project page hangs the conductor line lower by the string and shows, for every crossing, the distance of the lowest conductor line above its top.
- Suggest height difference
- Suggest height difference from ground and towers calculates it from the same data as the longitudinal profile: ground at both locations (terrain model) + top of foundation above ground (foundation) + lowest attachment (tower assembly; without one, 30 m assumed). The calculation is shown below the button; it is saved only with the form.
- Permissible conductor tension
- as a share of the breaking load in %, from the line design. If empty, the calculator only displays the maximum conductor tension.
Result
- Four tiles: stringing sag at the conductor temperature on the day, maximum sag, maximum conductor tension with its share of the breaking load, conductor length in the initial state with weight.
- Conductor curve: the span with the conductor in the initial state and in the states with the smallest and the largest sag – horizontally to scale, vertically exaggerated.
- Checklist: conductor tension, sag, lowest point, ruling span, calculation method, conductor data, preconditions. Each item is met, note, check or not permitted.
- Sag table: one row per state – −20, −5, +5, +10, +20, +40, +60 and +80 °C, plus the initial state, sagging and, if entered, the ice load: load, tensile stress, horizontal tension, tension at the attachment point, share of the breaking load, sag, conductor length. Copy values (for Excel) Subscription and Download as PDF Subscription output them.
- Conductor data and calculation: the conductor values used, the specific load, the tensile stress of the initial state and the formulas.
Purpose, assumptions and limits
- Purpose
- To follow on site which sag and which tension a conductor has at which temperature – for sagging, for sizing the stringing equipment and dead-ends, and for estimating the conductor length.
- Typical use
- Deriving the stringing sag for the day from a known state; cross-checking the designer's sag table; converting a measured sag into tension; estimating the sag in summer and under ice; tensions for winch, tensioner and temporary anchoring.
- For whom
- Overhead line construction, stringing, site management, work preparation.
- Units
- Span length, heights, sag and conductor length in m, conductor diameter in mm, cross-section in mm², conductor weight in kg/km, forces in kN, loads in N/m, tensile stress in N/mm², temperature in °C. Decimal comma and decimal point are both accepted.
- Assumptions
-
- The conductor hangs between two fixed attachment points as a catenary; it is perfectly flexible and uniformly loaded.
- Between two states the conductor length changes only through thermal expansion and elastic strain – with one modulus of elasticity and one expansion coefficient for the whole conductor.
- The ice load acts uniformly over the whole length, at −5 °C.
- Within a tension section the tensile stress is the same in all spans (suspension strings swing freely); the ruling span stands for this.
- Technical limits
-
- Not included: conductor creep and settling of new conductors (stringing allowances), wind, insulator and tension strings with their deflection, unequal tensile stresses in the spans of a section, conductor vibration.
- The calculator does not check clearances to ground, roads, buildings and crossing lines.
- The change-of-state equation uses the parabola. Up to a sag of about one tenth of the span length this is accurate enough; beyond that the checklist points it out.
- The permissible conductor tension is an input. The ice load is an input – or follows from the chosen ice load zone: the base value 5 + 0.1 · d N/m and the multiples 1, 2 and 4 of an earlier division into three zones are documented. The multiples 1 to 4 for today's four zones E1 to E4 are an assumption of even steps and have not been checked against the text of DIN EN 50341-2-4. So compare zone and ice load with the line design; if you know its value, enter it without a zone.
- The wind zone is information only: no wind load on the conductor, no blow-out. The values given (22.5 / 25.0 / 27.5 / 30.0 m/s and 0.32 / 0.39 / 0.47 / 0.56 kN/m²) apply at 10 m above flat, open terrain.
- The suggestion from the position is not a determination. The ice load is read from a map image (about 1.2 km per pixel; filled in from the surroundings under place names and along borders) – near boundaries, in narrow valleys and in high mountains it can be off. The zone map of DIN EN 50341-2-4 itself was not available. The line design remains decisive.
- Sources of the suggestion: municipal boundaries © BKG (2026) dl-de/by-2-0 (administrative areas 1:250 000, as of 1 Jan 2026; modified: one wind zone per municipality, rasterised to 500 m); DIBt, Zuordnung der Windzonen nach Verwaltungsgrenzen; data basis: Deutscher Wetterdienst (German Weather Service), map of ice loads on overhead lines from “Wind-, Eis- und Schneelasten” (B. Wichura, in: Forschungsfeld Naturgefahren, 2014, fig. 3), classes read from the map and rasterised (CC BY 4.0); VDE|FNN note “Auswertung von Eislastmessungen an Vogelschutzarmaturen” (12/2017).
- Permitted inputs: span length 5 to 2000 m, conductor temperature −40 to 100 °C (sagging up to 150 °C), horizontal tension 1 to 70 % of the breaking load, ice load up to 200 N/m.
- Standards
- Overhead lines above 1 kV are designed to EN 50341 with its national normative aspects; conductors are standardised in EN 50182. The conductor data in the calculator comes from a conductor manufacturer's table, modulus of elasticity and expansion coefficient from a reproduction of the former DIN 48204 – not from the texts of the standards. Catenary and change-of-state equation are textbook formulas of overhead line design.
- Data protection
- What is stored: the inputs, a summary of the result and who saved when – at the location, visible to everyone allowed to open the project. The calculator does not ask for personal data. More in the privacy policy.
Calculation method, formulas and example
With the horizontal tension H in N, the load w in N/m (conductor weight times 9.81, plus the ice load) and the span length a, the conductor hangs as a catenary with the parameter c = H ÷ w:
Sag: f = c · (cosh(a ÷ 2c) − 1) ≈ w · a² ÷ (8 · H)
Conductor length: L = 2c · sinh(a ÷ 2c) ≈ a + 8 · f² ÷ (3 · a)
If the attachment points are at different heights, the sag is the vertical distance between the conductor and the line joining the attachment points at mid-span; the conductor tension is highest at the higher attachment point (H · cosh of the distance from the lowest point, divided by c).
Change of state. With the tensile stress σ = H ÷ A, the specific load γ = w ÷ A (A conductor cross-section), the modulus of elasticity E and the coefficient of linear expansion α, the following holds between state 1 and state 2:
σ₂ − E · γ₂² · a² ÷ (24 · σ₂²) = σ₁ − E · γ₁² · a² ÷ (24 · σ₁²) − E · α · (t₂ − t₁)
The equation says: as the conductor gets longer when warmer, it hangs lower and loses tensile stress. The calculator solves it for σ₂ and calculates sag and length with the catenary again. For a tension section, a stands for the ruling span:
aid = √(Σa³ ÷ Σa) Example: spans of 250, 300 and 350 m → √(85 500 000 ÷ 900) = 308.2 m
| Quantity | Calculation | Result |
|---|---|---|
| Load | 0.985 kg/m · 9.81 | 9.663 N/m |
| Horizontal tension at 10 °C | 0.20 · 86.40 kN | 17.28 kN |
| Tensile stress σ₁, specific load γ | 17 280 N ÷ 282.54 mm²; 9.663 ÷ 282.54 | 61.16 N/mm²; 0.03420 N/(m·mm²) |
| Sag at 10 °C | 9.663 · 300² ÷ (8 · 17 280) | 6.29 m |
| Conductor length at 10 °C | 300 + 8 · 6.29² ÷ (3 · 300) | 300.35 m |
| Right-hand side for 40 °C | 61.16 − 77 000 · 0.03420² · 300² ÷ (24 · 61.16²) − 77 000 · 0.0000189 · 30 = 61.16 − 90.29 − 43.66 | −72.79 N/mm² |
| Tensile stress σ₂ at 40 °C | σ₂ − 337 732 ÷ σ₂² = −72.79 | 52.02 N/mm² → 14.70 kN |
| Sag at 40 °C | 9.663 · 300² ÷ (8 · 14 697) | 7.40 m |
| At −20 °C / at 80 °C | likewise | 21.14 kN, 5.14 m / 12.41 kN, 8.77 m |
| Sagging at 15 °C | likewise | 16.78 kN, 6.48 m |
With these inputs – they are the calculator's defaults – the page shows the same values. Between −20 and +80 °C the sag changes by 3.6 m here.
| Designation | to EN 50182 | Diameter | Weight | Cross-section | Breaking load | Stranding | Modulus | α |
|---|---|---|---|---|---|---|---|---|
| 35/6 | 34-AL1/6-ST1A | 8.1 mm | 140 kg/km | 40.08 mm² | 12.65 kN | 6/1 | 81 kN/mm² | 19.2 · 10⁻⁶/K |
| 44/32 | 44-AL1/32-ST1A | 11.2 mm | 373 kg/km | 75.65 mm² | 45.46 kN | 14/7 | 110 kN/mm² | 15.0 · 10⁻⁶/K |
| 50/8 | 48-AL1/8-ST1A | 9.6 mm | 196 kg/km | 56.29 mm² | 17.10 kN | 6/1 | 81 kN/mm² | 19.2 · 10⁻⁶/K |
| 50/30 | 51-AL1/30-ST1A | 11.7 mm | 378 kg/km | 81.02 mm² | 44.28 kN | 12/7 | 107 kN/mm² | 15.3 · 10⁻⁶/K |
| 70/12 | 70-AL1/11-ST1A | 11.7 mm | 284 kg/km | 81.29 mm² | 26.79 kN | 26/7 | 77 kN/mm² | 18.9 · 10⁻⁶/K |
| 95/15 | 94-AL1/15-ST1A | 13.6 mm | 383 kg/km | 109.72 mm² | 35.75 kN | 26/7 | 77 kN/mm² | 18.9 · 10⁻⁶/K |
| 95/55 | 97-AL1/56-ST1A | 16.0 mm | 714 kg/km | 152.81 mm² | 80.02 kN | 12/7 | 107 kN/mm² | 15.3 · 10⁻⁶/K |
| 105/75 | 106-AL1/76-ST1A | 17.5 mm | 899 kg/km | 181.22 mm² | 106.69 kN | 14/19 | 110 kN/mm² | 15.0 · 10⁻⁶/K |
| 120/20 | 122-AL1/20-ST1A | 15.5 mm | 494 kg/km | 141.42 mm² | 45.65 kN | 26/7 | 77 kN/mm² | 18.9 · 10⁻⁶/K |
| 120/70 | 122-AL1/71-ST1A | 18.0 mm | 904 kg/km | 193.40 mm² | 98.16 kN | 12/7 | 107 kN/mm² | 15.3 · 10⁻⁶/K |
| 125/30 | 128-AL1/30-ST1A | 16.3 mm | 590 kg/km | 157.76 mm² | 57.59 kN | 30/7 | 82 kN/mm² | 17.8 · 10⁻⁶/K |
| 150/25 | 149-AL1/24-ST1A | 17.1 mm | 604 kg/km | 173.10 mm² | 55.25 kN | 26/7 | 77 kN/mm² | 18.9 · 10⁻⁶/K |
| 170/40 | 172-AL1/40-ST1A | 18.9 mm | 794 kg/km | 211.84 mm² | 76.74 kN | 30/7 | 82 kN/mm² | 17.8 · 10⁻⁶/K |
| 185/30 | 184-AL1/30-ST1A | 19.0 mm | 744 kg/km | 213.63 mm² | 66.20 kN | 26/7 | 77 kN/mm² | 18.9 · 10⁻⁶/K |
| 210/35 | 209-AL1/34-ST1A | 20.3 mm | 848 kg/km | 243.19 mm² | 74.90 kN | 26/7 | 77 kN/mm² | 18.9 · 10⁻⁶/K |
| 210/50 | 212-AL1/49-ST1A | 21.0 mm | 979 kg/km | 261.54 mm² | 93.89 kN | 30/7 | 82 kN/mm² | 17.8 · 10⁻⁶/K |
| 230/30 | 231-AL1/30-ST1A | 21.0 mm | 874 kg/km | 260.76 mm² | 73.09 kN | 24/7 | 74 kN/mm² | 19.6 · 10⁻⁶/K |
| 240/40 | 243-AL1/39-ST1A | 21.8 mm | 985 kg/km | 282.54 mm² | 86.40 kN | 26/7 | 77 kN/mm² | 18.9 · 10⁻⁶/K |
| 265/35 | 264-AL1/34-ST1A | 22.4 mm | 998 kg/km | 297.75 mm² | 82.94 kN | 24/7 | 74 kN/mm² | 19.6 · 10⁻⁶/K |
| 300/50 | 304-AL1/49-ST1A | 24.4 mm | 1233 kg/km | 353.73 mm² | 105.09 kN | 26/7 | 77 kN/mm² | 18.9 · 10⁻⁶/K |
| 340/30 | 339-AL1/30-ST1A | 25.0 mm | 1174 kg/km | 369.14 mm² | 92.56 kN | 46/7 | 62 kN/mm² | 20.5 · 10⁻⁶/K |
| 380/50 | 382-AL1/49-ST1A | 27.0 mm | 1448 kg/km | 431.18 mm² | 123.05 kN | 54/7 | 70 kN/mm² | 19.3 · 10⁻⁶/K |
| 435/55 | 434-AL1/56-ST1A | 28.8 mm | 1647 kg/km | 490.59 mm² | 136.27 kN | 54/7 | 70 kN/mm² | 19.3 · 10⁻⁶/K |
| 450/40 | 449-AL1/39-ST1A | 28.7 mm | 1553 kg/km | 488.19 mm² | 120.74 kN | 48/7 | 62 kN/mm² | 20.5 · 10⁻⁶/K |
| 550/70 | 550-AL1/71-ST1A | 32.4 mm | 2085 kg/km | 620.90 mm² | 167.42 kN | 54/7 | 70 kN/mm² | 19.3 · 10⁻⁶/K |
| 560/50 | 562-AL1/49-ST1A | 32.2 mm | 1943 kg/km | 611.18 mm² | 148.99 kN | 48/7 | 62 kN/mm² | 20.5 · 10⁻⁶/K |
| 680/85 | 679-AL1/86-ST1A | 36.0 mm | 2564 kg/km | 764.53 mm² | 210.35 kN | 54/19 | 68 kN/mm² | 19.4 · 10⁻⁶/K |
| 1045/45 | 1046-AL1/45-ST1A | 43.0 mm | 3249 kg/km | 1090.86 mm² | 217.87 kN | 72/7 | 60 kN/mm² | 21.7 · 10⁻⁶/K |
Typical input errors:
- Conductor weight in kg/m: the field expects kg/km (985, not 0.985).
- Aluminium cross-section instead of total cross-section: for the conductor 240/40, 282.54 mm² counts, not 243.
- Air temperature instead of conductor temperature: in the sun and under current the conductor is warmer than the air. Measure the conductor temperature when sagging.
- Sloping length as span length: the span length is the horizontal distance.
- Single span instead of tension section: if the conductor hangs on suspension strings over several spans, the ruling span of the section belongs in the field.
- Share of breaking load read as tension: 20 means 20 % of the breaking load, not 20 kN.