Calculating cable pulling tension and sidewall pressure
Whether a cable goes through the route in one pull is decided at the bends. In a straight section the tension grows with the length – in a bend it is multiplied.
As of: · baustellen.tools
Straight section and gradient
With the cable weight m in kg/m, the coefficient of friction μ and g = 9.81 m/s², the tension over a straight section of length L with height difference Δh grows from F₁ to F₂ = F₁ + m · g · (μ · √(L² − Δh²) + Δh). On the level this leaves F₂ = F₁ + m · g · μ · L. Uphill, the whole weight of the section pulls as well; downhill, it helps.
The bend multiplies
In a bend with deflection angle φ (in radians), the capstan equation of Euler-Eytelwein applies: F₂ = F₁ · e^(μ · φ). With μ = 0.35, a 90° bend turns any incoming force into 1.73 times that force, a 180° bend into three times.
Two rules for practice follow from this: bends belong at the start of the pull, where there is still little force – and it is worth calculating both pulling directions.
Sidewall pressure and bending radius
In a bend the cable presses against the duct wall or the rollers: sidewall pressure = tension at the end of the bend ÷ radius, in N/m. The tool does not name a fixed limit for it – it depends on the cable design and is given in the data sheet. The smallest bending radius is a multiple of the cable diameter; in the example, 15 times.
Permissible tension
Common values from the installation instructions of a cable manufacturer: with a pulling eye on the conductors, 50 N/mm² of total conductor cross-section for copper and 30 N/mm² for aluminium; with a pulling grip on plastic-insulated cables without metal sheath and armour, the same values. For the cable actually used, the manufacturer's data sheet applies.
The coefficient of friction is the largest uncertainty
In a bend it sits in the exponent: 0.25 instead of 0.35 turns the factor at 90° into 1.48 instead of 1.73. Guide values from measurements by a lubricant manufacturer: in a duct with lubricant 0.09 to 0.11, without 0.22 to 0.35. A cautious planning value is 0.35 and more – always calculate with a higher value as well.
Example – recalculated by the program
80 m straight, 90° bend with 2 m radius, 40 m straight – one cable at 2.5 kg/m
Cable weight: 2.5 kg/mCoefficient of friction μ: 0.35Route: 80 m – 90° bend – 40 mPulling method: pulling grip, aluminium conductors 4 × 150 mm²
| Quantity | Calculation | Result |
|---|---|---|
| Pulling force from the long end | (2.5 · 9.81 · 0.35 · 80) · e^(0.35 · π/2) + 2.5 · 9.81 · 0.35 · 40 | 1.53 kN |
| Pulling force from the short end | the same calculation in the other direction: the bend comes earlier in the pull | 1.28 kN |
| Better pulling direction | 16 % less pulling force | from the short end |
| Permissible pulling force | from pulling method, conductor material and cross-section – or the manufacturer's value | 18.00 kN |
| Sidewall pressure in the bend | force at the end of the bend ÷ radius, in the better direction | 297 N/m |
A bend multiplies whatever is already pulling on the cable before it. That is why the tool always calculates both directions.
The figures are calculated by the same calculation core as in the application – every time this page is called up.
Limits
- An estimate, not a verification: the coefficient of friction is an assumption, the permissible tensions are common values.
- Bends lie in the horizontal plane; the self-weight of the cable in the bend is neglected.
- Not included: several cables in one duct with jamming, intermediate drives, elongation of rope and cable, water in the duct.
- When pulling, measure and record the tension and limit it at the winch.
This article is a working aid. It is not legal advice and does not replace specialist planning, a ground investigation report, structural analysis or a check by a competent person. The current editions of the standards and rules named here and the requirements of the client, the network operator and the authorities are authoritative. This is a translation; the rules cited are German and European ones, and the German version of this article prevails.
Sources and standards
- Formulas of static and rope friction (Euler-Eytelwein).
- Permissible tensions and bending radii: installation instructions and data sheets of cable manufacturers; for power cables they are governed by the standards of the DIN VDE 0276 series – the values in the tool are not taken from the text of the standards.
- Coefficients of friction: measurements by a lubricant manufacturer.
- Manual, chapter Cable route and cable pulling: calculation method, tables and example.
Calculate a cable pull with the route on the aerial image Calculation method in the manual
More articles
- Site layout plan: what belongs in it and how to build it up
- Slope angle and working space according to DIN 4124
- Calculating excavation and stockpiles
- Pipe trench: minimum width according to DIN EN 1610
- Escape and rescue plan: what belongs on the sheet
- Choosing a cable drum: how much cable fits on which drum?
- Sag and conductor tension in a span
- Foundation quantities for towers: concrete, formwork, excavation
- Swept path: will the delivery get round the corner?