Sag and conductor tension in a span
A conductor hangs lower in summer than in winter. How much lower is given by the change-of-state equation – and the sag follows from the ratio of conductor weight to tension.
As of: · baustellen.tools
The catenary
With the horizontal tension H in N, the load w in N/m (conductor weight times 9.81, plus ice load where applicable) and the span length a, the conductor hangs as a catenary with the parameter c = H ÷ w. The sag is f = c · (cosh(a ÷ 2c) − 1), to a good approximation f ≈ w · a² ÷ (8 · H). The conductor length is L = 2c · sinh(a ÷ 2c) ≈ a + 8 · f² ÷ (3 · a).
The change-of-state equation
Between two states – for example 10 °C when sagging and 80 °C in operation – the change-of-state equation links tensile stress σ, specific load γ, modulus of elasticity E and thermal expansion α: σ₂ − E · γ₂² · a² ÷ (24 · σ₂²) = σ₁ − E · γ₁² · a² ÷ (24 · σ₁²) − E · α · (t₂ − t₁).
In words: as the conductor gets longer when warmer, it hangs lower – and loses tensile stress in the process. The equation is solved for σ₂; sag and length again follow from the catenary.
Several spans: the ruling span
In a tension section with several spans, the tension equalises across the suspension insulator strings. The calculation then uses the ruling span a_id = √(Σa³ ÷ Σa). For spans of 250, 300 and 350 m this is 308.2 m.
Attachment points at different heights
If the attachment points are at different heights, the sag is the vertical distance between the conductor and the line connecting the attachment points at mid-span. The conductor tension is greatest at the higher attachment point.
Example – recalculated by the program
Conductor 243-AL1/39-ST1A, span 300 m, 20 % of the breaking load at +10 °C
Conductor: 243-AL1/39-ST1A (21.8 mm, 0.985 kg/m)Span: 300 mInitial state: horizontal tension 20 % of the breaking load at +10 °CConductor temperature when sagging: +15 °C
| Quantity | Calculation | Result |
|---|---|---|
| Sag in the initial state | catenary with H = 17.28 kN | 6.29 m |
| Stringing sag at +15 °C | change-of-state equation; horizontal tension 16.78 kN | 6.48 m |
| Greatest sag | at +80 °C | 8.77 m |
| Greatest conductor tension | at -20 °C, at the attachment point | 21.19 kN |
| Conductor length in the span | in the initial state | 300.35 m |
The sag table in the tool lists the temperatures from −20 to +80 °C, the initial state, the conductor temperature when sagging and – if entered – the ice load.
The figures are calculated by the same calculation core as in the application – every time this page is called up.
Limits
- What is calculated is one conductor between two fixed attachment points – without conductor creep, wind, insulator strings and stringing allowances.
- The values do not replace a line design calculation or the planner's sagging table; the tool does not verify minimum clearances.
- The conductor data come from the table of a conductor manufacturer; for execution, the data sheet of the conductor delivered applies.
This article is a working aid. It is not legal advice and does not replace specialist planning, a ground investigation report, structural analysis or a check by a competent person. The current editions of the standards and rules named here and the requirements of the client, the network operator and the authorities are authoritative. This is a translation; the rules cited are German and European ones, and the German version of this article prevails.
Sources and standards
- Catenary and change-of-state equation of the conductor (cable mechanics).
- Conductor data: table of a conductor manufacturer, designations according to EN 50182; modulus of elasticity and coefficient of expansion according to the conductor construction.
- Manual, chapter Span (conductor): calculation method, conductor table and example.
Calculate sag and conductor tension Calculation method in the manual
More articles
- Site layout plan: what belongs in it and how to build it up
- Slope angle and working space according to DIN 4124
- Calculating excavation and stockpiles
- Pipe trench: minimum width according to DIN EN 1610
- Escape and rescue plan: what belongs on the sheet
- Calculating cable pulling tension and sidewall pressure
- Choosing a cable drum: how much cable fits on which drum?
- Foundation quantities for towers: concrete, formwork, excavation
- Swept path: will the delivery get round the corner?