Skip to content

12 Cable drum

How much cable fits on a drum, and which drum does a cable length need: layers, capacity, weight – with a checklist and a comparison of all drum sizes.

Creating, calculating, saving

  • Create: on the location page, the card Cable drum › Create drum and calculate. There is one drum per location; the card then shows drum, cable length, capacity, layers and total weight, and Open takes you back.
  • Calculate: at the left the inputs in three groups – Cable, Drum, Winding –, at the right the result. Every change is calculated immediately. For an input that is not permitted, the page names the field and the range; the last valid result stays visible, faded.
  • Save or CtrlS stores inputs and result at the location; the time is shown next to it. If someone else has saved in the meantime, the page reports this and overwrites nothing.
  • Delete: on the location page in the menu ⋯ of the card. With the location, its drum is deleted, moved or archived as well.
  • Whoever has read-only access in the project can view and calculate but not save.

Inputs

Outer diameter of the cable
in mm, from the data sheet. For laid-up single-core cables or bundles, the diameter of the whole bundle.
Cable length
in m: the length to go on one drum.
Cable weight
in kg/m, from the data sheet. If the field is left empty, the weight is not checked.
Drum
Find the smallest suitable one takes the smallest drum in the table that takes both length and weight. Or choose a drum directly. Enter your own dimensions opens flange diameter, core diameter, traverse width (clear dimension between the flanges), weight of the empty drum and load capacity – for steel and special drums or other manufacturers.
Flange clearance
in mm: the distance to be kept free between the top layer and the flange edge so that the drum can be rolled and lagged. Default 50 mm – an assumption, not a figure from a standard.
Winding loss
in %: deduction from the calculated length because a cable never lies as tight as in the drawing. Default 10 % – an empirical value. With 0 % the calculator gives the pure geometry.
Smallest core diameter
as a multiple of the cable diameter, as specified by the cable manufacturer. If the field is left empty, the calculator only shows the ratio and checks nothing.

Result

  • Four tiles: drum with flange and core, capacity next to the required length, occupied and possible layers with the turns per layer, total weight of cable and empty drum.
  • Section through the drum, to scale: flanges, core, occupied layers dark, limit of the flange clearance dashed.
  • Checklist: drum selection, capacity, weight against load capacity, core diameter, flange clearance. Each item is met, note, check or not permitted.
  • Calculation: every quantity with value, unit and the formula with the numbers inserted. Copy values (for Excel) Subscription puts the table on the clipboard; Download as PDF Subscription produces a sheet for the file.
  • Drums compared: all drums in the table with layers, capacity and load capacity for this cable – and whether the required length fits, the drum is too small, does not carry the weight or has too small a core.
  • If the length fits on no drum, the checklist states how many drums of the size shown would be needed (part lengths).

Purpose, assumptions and limits

Purpose
To find the suitable drum size for a cable or check how much fits on an existing drum – with the weight that crane, drum trailer and vehicle have to carry.
Typical use
Ordering delivery lengths and drum sizes; rewinding remnants; defining part lengths for cable pulling; finding the transport and lifting weight; conductors and ducts on drums.
For whom
Cable and overhead line construction, work preparation, warehouse and logistics.
Units
Diameters and widths in mm, lengths in m, weights in kg and kg/m, winding loss in %. Decimal comma and decimal point are both accepted.
Assumptions
  • Neat layer winding: turn lies beside turn, layer on layer, and each layer adds exactly one cable diameter. If the cable settles into the gaps of the layer below, slightly more fits on the drum – the calculator stays on the safe side.
  • Partial turns and layers do not count: values are rounded down.
  • The flange clearance (50 mm) and the winding loss (10 %) are assumptions that can be changed. The calculator does not cite a standard for them.
  • The cable is round and of constant thickness along its length.
Technical limits
  • No statement on whether the cable tolerates the core diameter of the drum: the cable manufacturer states the smallest permissible core diameter and the bending radius. The calculator checks it only if you enter it.
  • The load capacity is that of the drum from the manufacturer's table. What is marked on the delivered drum is decisive; axle, pay-off stand, drum trailer and slings have to be verified separately.
  • Not included: lagging, pallets, protective caps, cable end seals; ribbon cables and flat cables; reels with a conical core.
  • Permitted inputs: cable diameter 2 to 250 mm, cable weight up to 100 kg/m, length 1 to 100,000 m, flange 200 to 5000 mm, core 50 to 4000 mm, traverse width 50 to 5000 mm, flange clearance up to 500 mm, winding loss up to 40 %.
Regulations
The dimensions of reels for cables, wires and conductors are governed by DIN 46391. The table in the calculator contains the reusable wooden drums of KABELTROMMEL GmbH & Co. KG (KTG) as published by the manufacturer (as of 11/2026) – not the text of the standard. The formula for the length is pure geometry.
Data protection
What is stored: the inputs, a summary of the result and who saved when – at the location, visible to everyone allowed to open the project. The calculator does not ask for personal data. More in the privacy policy.

Calculation method, formulas and example

With flange diameter d1, core diameter d2, traverse width L2 and cable diameter D:

usable winding height h = (d1 − d2) ÷ 2 − flange clearance      layers n = h ÷ D, rounded down      turns per layer w = L2 ÷ D, rounded down

In layer i the centre of the cable lies on the diameter d2 + (2i − 1) · D. One layer is therefore π · (d2 + (2i − 1) · D) · w long, all n layers together:

length = π · w · n · (d2 + n · D)      capacity = length · (1 − winding loss)

diameter of the winding = d2 + 2 · n · D      total weight = cable length · cable weight + empty drum

Drums in the calculator: reusable wooden drums by KTG (manufacturer's data, as of 11/2026)
ArticleFlange Ø d1Core Ø d2Traverse width L2Drum weightLoad capacity
10070710 mm355 mm400 mm25 kg250 kg
10080800 mm400 mm400 mm31 kg400 kg
10090900 mm450 mm560 mm47 kg750 kg
101001,000 mm500 mm560 mm71 kg900 kg
101201,250 mm630 mm670 mm144 kg1,700 kg
101401,400 mm710 mm670 mm175 kg2,000 kg
101601,600 mm800 mm850 mm290 kg3,000 kg
101801,800 mm1,000 mm840 mm380 kg4,000 kg
102002,000 mm1,250 mm1,045 mm550 kg5,000 kg
102082,000 mm1,000 mm1,060 mm479 kg5,000 kg
102202,240 mm1,400 mm1,140 mm710 kg6,000 kg
102502,500 mm1,400 mm1,140 mm875 kg7,500 kg
Example: 500 m of cable, 30 mm thick, 1.5 kg/m, smallest suitable drum, flange clearance 50 mm, winding loss 10 %
QuantityCalculationResult
Drum 10120 (1250 / 630 / 670 mm)h = (1250 − 630) ÷ 2 − 50 = 260 mm → 8 layers; 670 ÷ 30 → 22 turns; π · 22 · 8 · (630 + 8 · 30) mm = 481.0 m; − 10 %432.9 m – too small
Drum 10140 (1400 / 710 / 670 mm)h = (1400 − 710) ÷ 2 − 50 = 295 mm → 9 layers; 22 turns; π · 22 · 9 · (710 + 9 · 30) mm = 609.6 m; − 10 %548.6 m – fits
Occupied layersneeded 500 ÷ 0.9 = 555.6 m; 8 layers take π · 22 · 8 · (710 + 8 · 30) mm = 525.3 m9 layers
Diameter of the winding710 + 2 · 9 · 301250 mm, 75 mm below the flange edge
Weight500 · 1.5 = 750 kg cable + 175 kg drum925 kg; load capacity 2000 kg, 38 % utilised
Core to cable710 ÷ 3023.7

With these inputs the calculator shows the same values.

Typical input errors:

  • Conductor cross-section instead of outer diameter: what is meant is the diameter over the sheath in mm, not the cross-section in mm².
  • Weight in kg/km: data sheets often state kg/km – divide by 1000 (2350 kg/km are 2.35 kg/m).
  • Overall width instead of traverse width: for your own dimensions, the clear dimension between the flanges counts.
  • Total length instead of length per drum: the cable length is the one to go on one drum. For a route made of several part lengths, calculate each part length separately.
  • Winding loss set to 0: then the pure geometry applies – on site usually less fits.

Something missing or unclear? Write to info@baustellen.tools.